Product Overview
-
Product Summary
Product Range Revere AHG025-170HT High Temp Heat Pump Heating Capacity Range 25.76–177.69kW Maximum Heating Water Temperature 85°C Efficiency* Up to COP 2.0 (A20°C/W80°C) Refrigerant R32 + R515b (AHG025–103HT) / R410a + R515b (AHG170HT) Operating Ambient Range -35°C to +43°C Modular Design Yes (group control via centralised wired controller) NCC Section J Compliant Yes Environmental Comparison
Refrigerant GWP-100 Status R290 (Propane/HC) 3 Natural, future-proof R515B 299 Low GWP synthetic (non-flammable) R32 675 Low GWP synthetic R410A 2088 Being phased down R134a 1430 Being phased down -
Key Features

-
Performance & Efficiency
Key Components
Protection & Durability
-
-
Parameter Unit AHG025HT AHG050HT AHG062HT AHG103HT AHG170HT Electrical Power Supply V/P/Hz 380–415/3/50 380–415/3/50 380–415/3/50 380–415/3/50 380–415/3/50 Max. Power Input kW 13 25.9 32.4 54 90.8* Max. Current Input A 24 48 60 100 155.2* Heating Performance (A20°C/W80°C) Heating Capacity kW 27.73 52.9 56.9 113.42 177.69* Power Input kW 13.46 26.45 28.45 56.43 90.80* COP 2.0 2.0 2.0 2.0 1.96* Heating Performance (A7°C/W80°C) Heating Capacity kW 25.76 48.96 52.56 104.97 162.73* Power Input kW 13.35 27.20 29.20 58.00 90.31* Operating Range Operating Ambient Temp. °C -35 to +43 -35 to +43 -35 to +43 -35 to +43 -35 to +43 Max. Water Outlet Temp. °C 85 85 85 85 85 Refrigerant Type R32 + R515b R32 + R515b R32 + R515b R32 + R515b R410a + R515b Mechanical Compressor Scroll Scroll Scroll Scroll Scroll Hydraulic Water Flow Rate m³/h 4.25 8.5 10.63 17.72 22.4 Water Connections inch 1 1-1/4 1-1/2 2-1/2 3 Connection Type Threaded male (DN25) Threaded male (DN32) Threaded male (DN40) Flanged (DN65) — Circulation Water Pump Inbuilt No No No No No Sound Sound Power Level dB(A) 56 60 62 68 75 Physical Net Weight kg 260 410 525 835 1240 Dimensions (L × W × H) mm 1460×660×1360 1000×1000×2115 1760×880×1835 1986×1103×2055 2300×1200×2350 * AHG170HT values based on water outlet temperature of 75°C. The AHG170HT uses R410a + R515b refrigerant.
AHG170HT connection type not shown in AH brochure drawings — confirm with supplier.
Power/current input does not include water pump power/current input.
Specifications subject to change. In case of product improvements, the nameplate shall prevail.For installation, product dimensions and clearance details, please refer to the brochure under Documents tab.
-
-